CCHN favorable price 2 amp miniature circuit breaker is suitable for preventing potential damage to equipment and reducing the risk of fire or electrical hazards. 4 pole mini MCB breaker protects against both overload and short circuits, ensuring the safety and longevity of electrical systems.
4 Pole MCB Breaker Information
- Rated Current: 2 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 4 pole
- 6 kA rated short-circuit breaking capacity
- Compliant with IEC standard
- C curve trip characteristic
- With overload protection and short circuit protection function
Technical Data
| Model |
CCHN-NB8-634PC02 |
| Rated Current |
2A |
| Rated Voltage |
230/400V |
| Frequency |
50Hz |
| Number of Poles |
4P |
| Mechanical Life |
20000 Times |
| Electrical Life |
10000 Times |
| Rated Short-Circuit Breaking Capacity |
6000A |
| Operating Short-Circuit Breaking Capacity |
6000A |
| Rated Impulse Withstand Voltage (1.2/50) |
6kV |
| Dielectric Test Voltage |
2000V (50Hz, 1 min) |
| Heat & Humidity Resistance |
28 Cycles |
| Vibration Resistance |
No Obvious Vibration and Impact |
| Terminal Block |
Terminal Block Type |
Pillar Terminal Block |
| Min. Terminal Size Acceptability |
1mm2
|
| Max. Terminal Size Acceptability |
25mm2
|
| Standard Connection Torque |
2 N.m |
| Max. Tolerable Torque |
2.5 N.m |
| Wire Insertion Depth |
13mm |
| Reference Temperature |
30℃ |
| Operating Temperature |
-35℃~+70℃ |
| Storage Temperature |
35℃~+85℃ |
| Applicable Altitude |
2000m |
| Tripping Mode |
Thermal Magnetic Trip |
| Electromagnetic Tripping Type |
Type C (5In-10In) |
| Shell Flame Retardant Grade |
V0 |
| Wire Entry Method |
Both Upper and Lower |
| Installation Method |
TH35-7.5 Standard Rail |
| Protection Level |
Direct Installation |
IP20B |
| Installed in the Distribution Box |
IP40B |
4 Pole MCB Breaker Dimensions (Unit: mm)

Details

Tips: Basic requirements for the operating of a miniature circuit breaker
A miniature circuit breaker (MCB) is a crucial safety device in electrical systems, designed to protect circuits from overloads and short circuits. Here are the basic requirements for operating an MCB:
-
Correct Voltage Rating: Ensure the mini MCB matches the voltage rating of the system. Using an MCB with a lower voltage rating than the system can lead to malfunction and potential failure.
-
Appropriate Current Rating: Choose a micro circuit breaker with a current rating that aligns with the maximum expected load on the circuit. The MCB should be capable of handling normal operation without tripping, while still offering protection during overloads.
-
Proper Installation: Install the MCB in a standard distribution board with adequate space and ventilation to prevent overheating. Ensure it's securely connected to the circuit.
-
Periodic Testing: Regularly test the MCB by manually tripping it and checking its functionality to ensure it operates correctly in case of an overload or short circuit.
-
Avoid Frequent Overloading: Overloading an MCB can reduce its lifespan and lead to permanent damage.