Close
Shopping Categories
Search

75 hp (55 kW) AC Line Reactor, 3 Phase Output

The 150 amps AC line reactor operates at a frequency of 50/60 Hz, output3 phase. The material is divided into two types, copper and aluminum, power 75 hp (55 kW), strong anti-rust ability and good insulation effect.
SKU: CCHN-OLR-055
30-day Returns
Free Shipping
Delivery date: 6-25 days
3 phase output line reactor has voltage of 220V, 380V, 400V, 410V, 440V, 460V or 480V, 75 hp or 55kW, 50A for vfd, work freqency 50/60Hz. Affordable price, with safety and reliability.

55 kW 3-Phase Output Line Reactor Specifications

Basic Model CCHN-OCR-0150-047U-0.4SA
Recommended VFD Model GK3000-4T0550G (75 hp three phase VFD)
Phase 3 Phase
Power 75 hp (50 kW)
Weight 17 kg
Technical Parameters Work Voltage 380V (optional: 220V/ 240V/ 400V/ 415V/ 440V/ 460V/ 480V)
Work Frequency 50 Hz/60 Hz
Rated Current 150 A
Max Current 1.5 Times the Rated Current, Continued 60s
Inductance Value 0.047 mH
Material Aluminium/Copper (Optional)
Voltage Drop 2%
Noise ≤65dB
Insulation Class Class F, H
Protection Class IP00-IP22
Insulation Resistor ≥100MΩ
Working Environment Operation Environment -10℃~+45℃
Temperature Rise ≤85K
Humidity ≤90%RH, without condensation
Running Ambient Temperature -25℃~+45℃
Altitude ≤2000m

3-Phase Output Line Reactor Mounting Dimension

15hp (11kW) 3 phase line reactor

Dimension(±5mm)
L D W W1 H A×B
230 150 170 88 220 11×18

3-Phase Output Line Reactor Circuit Diagram

3 phase output line reactor circuit diagram

Tips: What are the advantages of CCHN output line reactors?

  • Increase the output high-frequency impedance, reduce the high-frequency leakage current, and protect the inverter.
  • Effectively reduce the high dv/dt output of the IGBT and extend the life of the motor.
  • Suppress the harmonic current output by the inverter.
  • Compensate for the influence of long-line distributed capacitance and extend the distance between input and output.
  • Reduce the noise of the motor.