| Model |
GS2-185 (220v, 240v), GS3-185 (380v, 400v, 415v), GS4-185 (460v, 480v), GS6-185 (550v, 690v). |
| Capacity |
250 hp (185 kw) |
| Current |
370 amps at 380v/480v, 710 amps at 220v |
| Weight |
21 kgs |
| Dimension |
525*257*194 mm |
| Input |
Voltage |
Three-phase 230v, 440v, 480v, 660v AC |
| Frequency |
50Hz/ 60Hz |
| Adaptive Motor |
Squirrel-cage three-phase asynchronous motor |
| Starting Times |
It is recommended not to exceed 20 times per hour. |
| 485 Communication |
DB9 interface, male plug, ① is RS485+, ⑥ is RS485- |
| Control Mode |
- Operation panel control.
- Operation panel + external control.
- External control.
- External control + COM control.
- Operation panel + external + COM control.
- Operation panel + COM control.
- COM control.
- No start or stop operation.
|
| Start Mode |
- Current-limiting to start.
- Voltage ramp to start.
- Torque control + current-limiting to start.
- Torque control + voltage ramp to start.
- Current ramp to start.
- Voltage current-limiting double closed-loop start.
|
| Stop Mode |
- Soft stop.
- Free stop.
|
| Protective Function |
- Open loop protection for external instantaneous stop terminals.
- Over-heat protection for soft starter.
- Protection for too long starting time.
- Input open phase protection.
- Output open phase protection.
- Unbalanced three-phase protection.
- Starting over current protection.
- Running overload protection.
- Under voltage protection for power voltage.
- Overvoltage protection for power voltage.
- Protection for fault parameter setting of the soft starter.
- Load short circuit protection.
- Auto restart or incorrect wiring protection.
- Incorrect wiring protection of external control stop terminals.
|
| Ambient |
Place to be used |
Indoor location with good ventilation free from corrosive gas and conductive dust. |
| Altitude |
Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. |
| Temperature |
-30 +55 oC |
| Humidity |
90%RH without dew condensation. |
| Vibration |
<0.5G |
| Structure |
Enclosure |
IP 20 |
| Cooling |
Natural wind cooling. |