Low price 25 kVA isolation transformer is designed to step down 3 phase voltage 380 volt to 3 phase 220 volt, also step up 220 volt to 380 volt vertion for selection, suitable for indoor applications.
25 kVA Isolation Transformer Specifications
| Basics |
Model |
CCHN-SG25KVA |
| Phase |
3 phase |
| Capacity |
25 kVA |
| Weight of Aluminium Wire Transformer |
Open type: 140kg Protected type: 165kg |
| Weight of Copper Wire Transformer |
Open type: 142kg Protected type: 168kg |
| Technical Parameters |
Primary Voltage |
380V (Optional: 120V/ 190V/ 208V/ 220V/ 230V/ 240V/ 380V/ 400V/ 415V/ 480V) |
| Secondary Voltage |
220V (Optional: 120V/ 190V/ 208V/ 220V/ 230V/ 240V/ 380V/ 400V/ 415V/ 480V) |
| Voltage Convert |
Three phase to three phase |
| Frequency |
50Hz / 60 Hz |
| Winding Material |
Aluminium/Copper wire (Optional) |
| Work Efficiency |
≥95% |
| Insulation Resistance |
≥50 MΩ |
| Electrical Strength |
3000V AC/1 min |
| Noise |
<35-65dB (1 meter) |
| Insulation Grade |
H level |
| Wiring Mode |
Dyn11 |
| Cooling Mode |
Dry type air cooling |
| Overload Capacity |
Allow more than 1.2 times rated load to work for up to 4 hours |
| Enclosure Protection Grade |
IP 24 |
| Certificate |
CE, ISO |
| Warranty |
12 months |
| Working Environment |
Temperature |
-15℃~+40℃ |
| Humidity |
≤90%RH, without condensation |
| Altitude |
<1000m, non corrosive gas and conductive dust |
Note:
Transformer can only convert voltage and CANNOT convert frequency.
Transformer CANNOT convert single phase voltage to 3 phase voltage.
Input/output voltage, power rating and whether with shell of all transformers, can be customized according to clients' requirements.
3 Phase Isolation Transformer Schematic Diagram

3 Phase Isolation Transformer Details

25 kVA Isolation Transformer Installation Dimension

| Aluminium Wire Transformer Size |
Copper Wire Transformer Size |
| Open type: a*b*c=440*330*430mm |
Open type: a*b*c=440*330*420mm |
| Mouting size: d*e=300*185mm |
Mouting size: d*e=300*185mm |
| Protected type: A*B*C=420*610*610mm |
Protected type: A*B*C=420*610*610mm |
Tips: How to select a 3 phase step up & step down isolation transformer?
- Confirm the power supply voltage (V) provided by the grid and the required input rated voltage of the electric equipment to determine the voltage (V) ratio of the transformer.
- Confirm the phase number of the input power supply required by electrical equipment to determine whether to make three-phase or single-phase system transformer.
- Confirm the required input rated current (A) of the electrical equipment to determine the transformer capacity (KVA).
- Insulation class requirements: A class 105 ℃, B class 130 ℃, F class 155 ℃, H class 180 ℃.
- Autotransformer or isolated transformer.